F-Gas Compliance

aces – “where every problem has a solution”

Or you can visit our online shop to purchase click here

We don’t just design walls,
We create ambience.

F-Gas Compliance ‘We (ACES) Are Fully Compliant And Registered’

F Gas Compliance – ACES can make you compliant! Call Us Today
. Frequency of Leak Checks
. No Leakage Detection System Leakage Detection Systems
5 tonnes CO2-eq 12 months 24 months
50 tonnes CO2-eq 6 months 12 months
500 tonnes CO2-eq 3 months 6 months

OBJECTIVE

The legal responsibility for compliance is on the end user or operator of the equipment using the gases covered in scope but the second version of the legislation (EC517/2014) also crucially has legal responsibility for some aspects placed upon contractors. This technical bulletin is aimed at advising members of what they need to do to comply.

Failure to comply with this legislation could result in a fine up to £5,000 if the case is tried in a Magistrates’ Court, and an unlimited fine if tried in a Crown Court.

The contractor – both the individual engineer/technician attending site and the company employing that engineer/technician – must be certified in F Gas to carry out certain tasks such as installation, maintenance, service, repair, decommissioning, leakage checking and recovery of gases on stationary refrigeration, air conditioning and heat pump equipment and movable room air conditioning appliances.

EQUIPMENT IN SCOPE AND LEAKAGE CHECKING REQUIREMENTS

The requirement for, and frequency of, leak checks are determined by the CO2-eq of the total charge of the system as determined by the GWP (global warming potential) of the gas in the system. The intervals between leak checks can be doubled by fitting appropriate automatic leak detection systems.

A leakage detection system is defined as “a calibrated mechanical, electrical or electronic device for detecting leakage of fluorinated greenhouse gases which, on detection, alerts the operator.

Refrigerant GWP 5 tonnes CO2-eq (kg) 50 tonnes CO2-eq (kg) 500 tonnes CO2-eq (kg)
R32 675 7.407 74.074 740.741
R134a 1430 3.497 34.965 349.650
R245fa 1030 4.854 48.544 485.437
R404a 3922 1.275* 12.749 127.486
R407A 2107 2.373* 23.73 237.304
R407C 1774 2.818* 28.185 281.849
R407F 1850 2.703* 27.027 270.27
R410A 2088 2.395* 23.946 239.464
R422D 2729 1.832* 18.322 183.217
R437A 2550 1.961* 19.608 196.078
R507A 3985 1.255* 12.547 125.471
R1234yf 4 1,250 12,500 125,000
R1234ze 7 714.286 7,142.857 71,428.571