Daikin Chiller Pressure Leak Test (PLT)

Daikin Chiller Pressure Leak Test (PLT)

Job Description: Daikin Chiller Pressure Leak Test (PLT)

Area: Green Park, Reading

Issue Identified: Following a recent call out, our engineer found both circuits to be in low pressure fault. We attended site to perform a Pressure Leak Test (PLT) using Oxygen Free Nitrogen (OFN) to locate the leak and repair.

Works carried out:

  • Isolated the Daikin Chiller unit electrically and mechanically.
  • Recovered refrigerant from into a dedicated recovery cylinder.
  • Pressure tested with OFN.
  • Identified the leak on oil filter housing and replaced the gasket.
  • Repaired leak by means of tightening of a fitting.
  • Retested with OFN (oxygen free nitrogen) following the repair.
  • Once proved released OFN to the atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with virgin refrigerant.
  • Repeated on Circuit 2.
  • Test ran and re-commissioned.
  • Completed waste transfer note and handed to an on-site representative.
  • Completed F Gas certificate.