Pressure Leak Test on a Carrier Chiller

Pressure Leak Test on a Carrier Chiller

Job Description: Pressure Leak Test on a Carrier Chiller

Area: Globeside Business Park, Marlow

Issue Identified: Following a recent call out engineer had advised that the chiller tripped due to the high oil pressure. Circuit 2 was also showing low oil level.

Pressure Leak Test

Scope of Works Carried Out:

  • Isolated the Carrier Chiller electrically and mechanically.
  • Recovered refrigerant from Circuit A into a dedicated recovery cylinder.
  • Weighed and confirmed charge in the circuit.
  • Drained oil out of the system.
  • Removed and replaced oil filters.
  • Pressure test with OFN (oxygen free nitrogen).
  • Repaired the leak by means of tightening.
  • Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charge with recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas certificate.
  • Repeated for Circuit B.