Pressure Leak Test on a Ciat Chiller

Pressure Leak Test on a Ciat Chiller

Job Description: Pressure Leak Test on a Ciat Chiller

Area: Isle of Dogs, London

Issue Identified:  We quoted for a detailed pressure leak test as per the service report from recent planned preventative maintenance visit

Works carried out:

  • Recovered refrigerant into certified cylinder.
  • Weighed and confirmed the system charges.
  • Charged the system with OFN (Oxygen Free Nitrogen).
  • Found liquid valve and suction service valve leaking.
  • Repaired and retested
  • Once proven the unit was leak tight released the OFN (oxygen free nitrogen).
  • Evacuated system to a minimum of 2 Torr.
  • Re-charged the unit with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed all waste paperwork.
  • Cleared site of any waste created.
Ciat Chiller Features

The AQUACIAT Chillers have been adapted for heating and air conditioning applications in the fields of Offices, Healthcare, Industry, Administration, and Commercial  buildings.

These units are designed for outdoor installation and do not require protection from adverse weather conditions.

To operate in COOLING or HEATING mode, these units use outside air as the only external source, this permits the evacuation of heat in summer or the supply of thermal energy for heating in winter.

Some of the many Ciat Chillers we support
  • AQUACIAT POWER ILD R32
  • AQUACIAT LD R32
  • AQUACIAT POWER LD R32
  • POWERCIAT LX R134a
  • AQUACIAT LD R410A
  • AQUACIAT Free Cooling
  • AQUACIAT Power R410A
  • CIAT Cooler R-410A
  • AQUACIAT2 HYBRID R-410A
  • AQUACIAT Caleo
  • GEOCIAT Modular
  • DynaCIAT Power
  • HydroCIAT LW
  • HydroCIAT TURBO LWT
Abbreviations

HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test,  PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning,  HP – High Pressure, LP – Low Pressure

Ref: 1927