Pressure Leak Test (PLT) on Daikin AC Unit

Pressure Leak Test (PLT) on Daikin AC Unit

Job Description: Pressure Leak Test (PLT) on Daikin AC Unit

Area: Jermyn Street, London

Issue Identified: Following a recent call out, our engineer had advised that the unit is running on low pressures, indicating a shortage in refrigerant. We attended site to perform a leak test and fix any leaks found to correct this issue.

Pressure Leak Test

Works carried out:

  • Isolated the Daikin unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Pressure tested with OFN (oxygen free nitrogen) to locate leak.
  • Repaired the leak on the liquid like service port.
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate