PRV Replacements on 3 Turbocor Chillers

PRV Replacements on 3 Turbocor Chillers

Job Description: PRV Replacements on 3 Turbocor Chillers

Area: Overton Mill, Basingstoke

Issue Identified: Following a recent visit to site it was found Pressure Relief Valves were out of date on 3 Turbocor Chillers.

Scope of Works Carried Out:

  • Closed the discharge and liquid service valves and decanted the charge over to the evaporator side of the system.
  • Replaced the PRV (pressure relief valves) fitted to the chiller.
  • Commissioned the chiller back to service.
  • Completed each chiller on consecutive days to keep works across the chillers to a minimum i.e. not working on several in a day and risking the load.
  • PRV (pressure relief valves) fitted were high side PRV 2 x 20 bar 1/2″ x 1″ g14/s, 2 x 20 bar 1″ x 1-1/4″ g20/s, low side manifold 2 x 16bar 3/4″-1″ g14/s.
  • All PRV (pressure relief valves) included certificates of conformity.

Some of the many Turbocor Chillers we support
  • 0301A
  • 0401A
  • 0532A
  • 0632A
  • 0752A
  • 0903A
  • 1103A

ACES Also Supply And Install New Chillers – Call Us For More Information 01865 890996

Abbreviations

HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test,  PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning,  HP – High Pressure, LP – Low Pressure