Replace Expansion Valve on a Climaveneta Chiller

Replace Expansion Valve on a Climaveneta Chiller

Job Description: Replace Expansion Valve on a Climaveneta Chiller

Area: Verde Building, London

Issue Identified:  Following a recent maintenance on site the engineer advised that the Climaveneta chiller had a leak on the expansion valve and required replacing

Expansion Valve

Works carried out:

  • Isolated the Climaveneta unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Pressure tested with OFN (oxygen free nitrogen) to locate leak.
  • Repaired the leak by means of brazing.
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.