Replace High Pressure Switch and Sensor on a Mitsubishi- PUHY

Job Description: Replace High Pressure Switch and Sensor on a Mitsubishi- PUHY

Area: High Holborn, London

Issue Identified: Following a recent call out to site our engineer noted that the unit was very short on refrigerant. Our engineer also checked the high-pressure switches and found they were out of calibration.

Works carried out:

  • Isolated the Mitsubishi PUHY Unit electrically and mechanically.
  • Recovered refrigerant from the Mitsubishi PUHY Unit into a dedicated recovery cylinder.
  • Checked and confirmed charge.
  • Replaced the high-pressure switch and sensor.
  • Pressure tested with (oxygen free nitrogen) OFN.
  • Located the leak and repaired by means of tightening.
  • Re-charged the unit with (oxygen free nitrogen) OFN to confirm the unit is leak tight.
  • Once proved released (oxygen free nitrogen) OFN to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas certificate.