Replace Pressure Relief Valves on a Ciat Chiller
Job Description: Replace Pressure Relief Valves on a Ciat Chiller
Area: Abingdon, Oxfordshire
Asset: Ciat Chiller
Issue Identified: Following a recent visit and fault investigation on the Ciat Chiller our engineer advised to carry out a pressure leak test carried out on the asset and pressure relief valve to be replaced as it was out of date and potentially the cause of the leak.
Works carried out:
- Isolated the Ciat Chiller electrically and mechanically.
- Recovered 8kgs refrigerant into certified cylinder for storage on site.
- Fitted new Pressure Relief Valve rated at 44 Bar.
- Topped up system with 3L of POE VG32 lubricant.
- Pressure tested with OFN (oxygen free nitrogen).
- Found leak on suction service port.
- Replaced Schrader and retested.
- Left system under test overnight.
- No further leaks found.
- Fitted new discharge transducer.
- Released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
- Re-charged with recovered refrigerant and trim charged with virgin refrigerant.
- Test ran and commissioned.
- Completed waste transfer note and handed to on-site representative.
- Completed F Gas records.

Some of the many Ciat Chillers we support
- AQUACIAT POWER ILD R32
- AQUACIAT LD R32
- AQUACIAT POWER LD R32
- POWERCIAT LX R134a
- AQUACIAT LD R410A
- AQUACIAT Free Cooling
- AQUACIAT Power R410A
- CIAT Cooler R-410A
- AQUACIAT2 HYBRID R-410A
- AQUACIAT Caleo
- GEOCIAT Modular
- DynaCIAT Power
- HydroCIAT LW
- HydroCIAT TURBO LWT
ACES Group Can Also Supply and Install New Chillers – Call Us On 01865 890996

Ciat Chiller Features
The AQUACIAT Chillers have been adapted for heating and air conditioning applications in the fields of Offices, Healthcare, Industry, Administration, and Commercial buildings.
Some Ciat Chillers are designed for outdoor installation and do not require protection from adverse weather conditions.
To operate in COOLING or HEATING mode, these units use outside air as the only external source, this permits the evacuation of heat in summer or the supply of thermal energy for heating in winter.
Abbreviations
HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test, PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning, HP – High Pressure, LP – Low Pressure
Ref: 2077