Replace Sight Glass and Pressure Leak Test on a York Chiller

Job Description: Replace Sight Glass and Pressure Leak Test on a York Chiller

Area: Charles II Street, London

Issue Identified:  Following a recent maintenance visit, our engineer found the system to be leaking from the sight glass on the liquid line, he noted the system required a pressure test and a new sight glass. The engineer also advised that the chiller required all contactors to be replaced due to pitting.

Works carried out:

  • Isolated the unit electrically and mechanically.
  • Recovered any remaining refrigerant.
  • Weighed and confirmed the charge.
  • Replaced the sight glass.
  • Pressure tested with OFN (oxygen free nitrogen) to locate leak.
  • Repaired the leak by means of brazing.
  • Once proved release OFN to the atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with recovered refrigerant, and trim charged with virgin refrigerant.
  • Replaced the contactors.
  • Test ran and commissioned.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas certificate.