Water Sensor Replacement & PRV Replacement on a Ciat Chiller
Job Description: Water Sensor Replacement & PRV Replacement on a Ciat Chiller
Area: Culham, Abingdon, Oxfordshire
Issue Identified: Following a recent planned preventative maintenance visit our engineer advised that the Ciat Chiller on circuit 1 required a pressure leak test, he has also advised that the pressure relief valves required replacement and water sensor required replacement.
Works carried out:
- Isolated the unit electrically and mechanically.
- Recovered refrigerant into certified cylinder for storage on site.
- Weighed and confirmed the charge.
- Removed and replaced pressure relief valves.
- Removed and replaced flow sensor.
- Pressure tested with OFN (oxygen free nitrogen) to locate any leaks.
- Discovered leak on the bottom of the condenser coil, brazed and re pressure tested.
- Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
- Re-charged with recovered refrigerant and trim charged with virgin refrigerant.
- Test ran and commissioned.
- Completed waste transfer note and handed to on-site representative.
- Completed F Gas records.

ACES Group Can Also Supply and Install New Chillers – Call Us On 01865 890996
Ciat Chiller Features
The AQUACIAT Chillers have been adapted for heating and air conditioning applications in the fields of Offices, Healthcare, Industry, Administration, and Commercial buildings.
These units are designed for outdoor installation and do not require protection from adverse weather conditions.
To operate in COOLING or HEATING mode, these units use outside air as the only external source, this permits the evacuation of heat in summer or the supply of thermal energy for heating in winter.

Some of the many Ciat Chillers we support
- AQUACIAT POWER ILD R32
- AQUACIAT LD R32
- AQUACIAT POWER LD R32
- POWERCIAT LX R134a
- AQUACIAT LD R410A
- AQUACIAT Free Cooling
- AQUACIAT Power R410A
- CIAT Cooler R-410A
- AQUACIAT2 HYBRID R-410A
- AQUACIAT Caleo
- GEOCIAT Modular
- DynaCIAT Power
- HydroCIAT LW
- HydroCIAT TURBO LWT
Abbreviations
HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test, PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning, HP – High Pressure, LP – Low Pressure