Bitzer Compressor Replacement on a Lennox Chiller

Bitzer Compressor Replacement on a Lennox Chiller

Job Description: Bitzer Compressor Replacement on a Lennox Chiller

Area: The Forum, Portsmouth

Issue Identified:  Following a request from client to replace failed Bitzer Compressor on a Lennox Chille

Works carried out:

  • Isolated the Lennox Chiller unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • ACES Lift and Shift Team removed compressor from the chiller bed
  • We replaced with a service exchange Bitzer CSH 7571 90Y part wind Screw Compressor
  • Pressure tested with OFN (oxygen free nitrogen) to locate leak.
  • Repaired the leak by means of brazing.
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.
Bitzer Compressor Replacement