Bitzer CSH 7571 90Y Compressor Replacement to a Lennox Chiller

Bitzer CSH 7571 90Y Compressor Replacement to a Lennox Chiller

Job Description: Bitzer CSH 7571 90Y Compressor Replacement to a Lennox Chiller

Area: The Forum, Portsmouth

Issue Identified: Following an enquiry from customer we quoted to replace a failed compressor.

Lennox Chiller

Scope of Works Carried Out:

  • Isolate the Lennox Chiller unit electrically and mechanically.
  • Recovered refrigerant from the Lennox Chiller into a dedicated recovery cylinder.
  • Weighed and confirmed charge.
  • ACES Lift and Shift Team removed the compressor from the chiller bed.
  • Replaced the compressor with service exchange Bitzer CSH 7571 90Y part wind screw compressor.
  • Charged the system with oxygen free nitrogen (OFN) to prove leak tight.
  • Repaired a minor leak by tightening.
  • Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with recovered refrigerant.
  • Test ran and re-commissioned.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas certificate.