Carrier Chiller 30RB0302 Repairs in Mark Lane, London

in Chiller Repairs 

Asset: Carrier Chiller 30RB0302

Area: Mark Lane, London

Issue Identified: Following a recent maintenance on site the engineer found some issues with the chiller. There was a lot of corrosion on the coils, oil deposits were found around the discharge valves and the expansion valves. Both circuits had failed crankcase heaters.

Works carried out:

  • Isolated the unit electrically and mechanically.
  • Recovered the refrigerant into a dedicated recovery cylinder.
  • Replaced the crankcase heaters.
  • Pressure tested with OFN (oxygen free nitrogen) to locate leak.
  • Repaired leak by means of brazing over of a pipe only.
  • Re-Pressure tested with OFN (oxygen free nitrogen) to prove system was leak tight.
  • Once proved released OFN to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charged with virgin refrigerant.
  • Test ran and re-commissioned
  • Replaced compressor fuses.
  • Replaced mains isolator.
  • Repeated for other circuit.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas certificate.