Chiller Repairs to a York Chiller in New Street Square, London

in Chiller Repairs 

Asset: York Water Chiller

Area: New Street Square, London

Issue Identified: Following a recent 4-hour response reactive air-conditioning and chiller call out our engineer found the system pressures were below the recommended parameters. We recommended a pressure leak test to confirm the refrigerant leakage location.

Works carried out:

  • We isolated the unit electrically and mechanically.
  • We recovered refrigerant down to 1 psi into a dedicated recovery cylinder for weighing.
  • We repaired the leak by means of brazing over of a pipe only.
  • We re-pressure tested with OFN (oxygen free nitrogen) to prove system is leak tight for a minimum of 24hrs.
  • Once proved we released OFN to the atmosphere and evacuated the system to a minimum of 2 torr.
  • We re-charged with virgin refrigerant
  • We carried out leak test as per F Gas regulations.
  • Test ran and re-commissioned
  • Left system running ok