Clivet Chiller Pressure Leak Test
Job Description: Clivet Chiller Pressure Leak Test
Area: Stable Street, London
Issue Identified: Following a recent call out to site the engineer advised that the refrigerant charge has been lost from the Clivet Chiller.
Works carried out:
- Recovered any remaining refrigerant from the Clivet Chiller into certified cylinder.
- Weighed and confirmed the system charges.
- Fractured pipework found.
- Replaced suction pipework.
- Charged the system with OFN (Oxygen Free Nitrogen).
- Once proven the unit was leak tight following repair released the nitrogen.
- Evacuated system to a minimum of 2 Torr.
- Re-charged the unit with recovered refrigerant and topped up with virgin refrigerant.
- Test ran and re-commissioned.
- Completed all waste paperwork.

Abbreviations
HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test, PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning, HP – High Pressure, LP – Low Pressure