Job Description: Coil Repair on Climaveneta Chiller

Area: Haymarket, London

Issue Identified: Following a recent engineer attendance and investigation the engineer found that there was a leak on the condenser tube on the coil.

Climaveneta Chiller

Works carried out:

  • Isolated the Climaveneta Chiller unit electrically and mechanically.
  • Carried out the repair on the coil which included hot works.
  • Pressure tested the system with OFN (oxygen free nitrogen).
  • Repaired further leaks on the coil by means of brazing. Further leaks were found on the compressor housing which were quoted to the client.
  • Once proved released OFN (oxygen free nitrogen to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas records.