Coil Repair on Climaveneta Chiller
Job Description: Coil Repair on Climaveneta Chiller
Area: Haymarket, London
Issue Identified: Following a recent engineer attendance and investigation the engineer found that there was a leak on the condenser tube on the coil.

Works carried out:
- Isolated the Climaveneta Chiller unit electrically and mechanically.
- Carried out the repair on the coil which included hot works.
- Pressure tested the system with OFN (oxygen free nitrogen).
- Repaired further leaks on the coil by means of brazing. Further leaks were found on the compressor housing which were quoted to the client.
- Once proved released OFN (oxygen free nitrogen to atmosphere and evacuated system to a minimum of 2 Torr.
- Re-charged with virgin refrigerant.
- Test ran and re-commissioned.
- Completed waste transfer note and handed to on-site representative.
- Completed F Gas records.