Job Description: Compressor Overhaul to a Bluebox Chiller
Issue Identified: Following a call out, the engineer advised that the chiller 2 compressor was in alarm and required an overhaul.

Works carried out:
- Isolated the unit electrically and mechanically.
- Recovered the refrigerant into a dedicated recovery cylinder.
- Checked and confirmed the charge.
- Lifting team attended site and removed the compressor from the chiller bed.
- Compressor engineer attended site and stripped the compressor.
- Checked all parts for wear and clearances.
- Removed the winding from site for testing and repair.
- Renewed all the gaskets and seals.
- Returned to site and started rebuilding the compressor.
- Lifting team reinstated the compressor on chiller bed.
- Pressure tested with OFN (oxygen free nitrogen).
- Repaired the leak by means of brazing.
- Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
- Re-charged with recovered refrigerant.
- Test ran and re-commissioned.
- Completed waste transfer note and handed to on-site representative.
- Completed F Gas certificate.
ACES is now one of the largest compressor remanufacturing companies in the UK. Our success is attributed to a team of people who have spent most of their working lives in the compressor remanufacturing field. This experience makes us the first choice for customers who demand quality and value for a remanufactured compressor.