Compressor Replacement on a Systemair Chiller and Replace Suction Gasket on Circuit 2

Compressor Replacement on a Systemair Chiller and Replace Suction Gasket on Circuit 2

Job Description: Compressor Replacement on a SystemAir Chiller and Replace Suction Gasket on Circuit 2.

Area: Aldersgate Street, London

Issue Identified: Following a recent callout our engineer advised the compressor had failed and required to be replaced.

Systemair Chiller

Scope of Works Carried Out:

  • Decanted the SystemAir Chiller refrigerant into cylinders and weighed for F gas records.
  • ACES Lift and shift removed the compressor from the bed and lifted the new one up onto the bed.
  • Pressurised the system with OFN (oxygen free nitrogen) and checked for leaks.
  • Repaired any leak found.
  • Evacuated the system.
  • Added a virgin charge of refrigerant to the system and commissioned.

Chiller 1 circuit 2:

  • Decanted the system into cylinders and weighed for F gas records.
  • Replaced the faulty suction gasket to the compressor.
  • Pressurised the system with OFN (oxygen free nitrogen) and checked for leaks.
  • Repaired any leak found.
  • Evacuated the system.
  • Added a virgin charge of refrigerant to the system and commissioned.
  • Clear site and completed all F Gas paperwork