Compressor Replacement on Daikin Chiller

Compressor Replacement on Daikin Chiller

Job Description: Compressor Replacement on Daikin Chiller

Area: Crespigny Park, London

Issue Identified:  Following a recent enquiry for ACES to carry out refrigerant works associated with replacing a failed Daikin Screw Compressor

Daikin Chiller

Works carried out:

  • Isolated the Daikin Chiller unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • ACES lift and Shift Team removed and replaced Daikin Screw Compressor.
  • Replaced liquid drier cores.
  • Pressure tested with OFN (oxygen free nitrogen)
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.