Condenser Coil Replacement on a Mitsubishi DX Condenser
Job Description: Condenser Coil Replacement on a Mitsubishi DX Condenser
Area: Pans Peninsula, London
Issue Identified: Following a recent planned preventative maintenance visit our engineer advised that the condenser coil is leaking and required replacement.
Works carried out:
- Isolated the Mitsubishi DX Condenser unit electrically and mechanically.
- Removed and stored refrigerant into specified cylinders.
- Removed the leaking coil and stored it for disposal.
- Installed new coil by means of brazing.
- Re-pressure test with OFN (oxygen free nitrogen) for 24 hours to prove system was leak tight.
- Once proved release OFN to atmosphere and evacuated system to a minimum of 1.4 Torr.
- Re-charged with 27kg R410A refrigerant.
- Test ran and re-commissioned.
- Completed waste transfer note and handed to on-site representative.

ACES Group Can Also Supply and Install all Mitsubishi Air-Conditioning Units – Call Us On 01865 890996
Mitsubishi Mr Slim – is available as wall or floor mounted and is ideal for retail and offices
M Series – a very versatile system and is suitable for retail and offices and is available using low GWP R32 refrigerant
Multi Split – the outdoor unit can connect between 2 and 11 indoor units.
City Multi VRV – ideal for larger premises who demand efficiency and high performance
City Multi HVRF – a multi hybrid VRV system which can provide heating in one area and cooling in another area of building

Some of the many Mitsubishi Split units we support
- PUZ-ZM200/250YKA R32 Power Inverter Heat Pump
- PUZ-M200/250YKA R32 Standard Inverter Heat Pump
- PLA-ZM R32 Power Inverter Heat Pump
- PLA-M R32 Standard Inverter
- PLA-ZM R32 Power Inverter Heat Pump
- PLA-M R32 Standard Inverter
- PLA-SM R32 Inverter Heat Pump
- PKA-M R32 Power Inverter Heat Pump
- PKA-M R32 Standard Inverter Heat Pump
- SLZ-M R32 Inverter Heat Pump
- PEAD-M R32 Power Inverter Heat Pump
- PEAD-M R32 Power Inverter Heat Pump
- PEAD-M R32 Standard Inverter Heat Pump
- PEAD-M R32 Standard Inverter Heat Pump
- SEZ-M R32 Inverter Heat Pump
- PEA-RP R410A Power Inverter Heat Pump
- PEA-RP R410A Standard Inverter Heat Pump
- PAC-IF013B-E Air Handling Unit Controller
Abbreviations
HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test, PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning, HP – High Pressure, LP – Low Pressure
Ref: 2279