Daikin Chiller Pressure Test

Daikin Chiller Pressure Test

Job Description: Daikin Chiller Pressure Test

Area: Oak Way, Reading

Issue Identified:  Following a recent call out our engineer found both circuits to be in Low Pressure Fault.

Pressure Test

Works carried out:

  • Isolated the Daikin Chiller unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Pressure tested with OFN (oxygen free nitrogen)
  • Leak found on the oil filter housing.
  • Replaced gasket
  • Left on pressure test overnight.
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.