Denco Unit Repairs
Job Description: Denco Unit Repairs
Area: St James Market, London
Issue Identified: Following a recent call out the engineer advised that the Denco Unit had lost all its refrigerant and required a pressure leak test to locate any leaks.
Works carried out:
- Isolated the unit electrically and mechanically.
- Pressure tested the system with OFN (oxygen free nitrogen) to confirm leak.
- Leak found on cracked joint pipe leaving evaporator coil.
- Effect welded repair and replaced filter drier and re-tested with nitrogen.
- Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
- Re-charged with refrigerant.
- Test ran and re-commissioned.
- Completed waste transfer note and handed to on-site representative.
- Completed F Gas records

Abbreviations
HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test, PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning, HP – High Pressure, LP – Low Pressure