Detailed Pressure Leak Test on a Ciat Water Chiller
Job Description: Detailed Pressure Leak Test on a Ciat Water Chiller
Area: St James Street, London
Issue Identified: Following a recent callout, we quoted to carry out a detailed pressure leak test of the Ciat Water Chiller system.

Scope of Works Carried Out:
- Decanted the Ciat Water Chiller system into cylinders.
- Weighed for F gas records – System was noted at 118kg of R407c.
- Pressurised the system with OFN (oxygen free nitrogen) and checked for leaks.
- Repaired any leaks found.
- Evacuated the system.
- Added a virgin charge of refrigerant to the system and commissioned.
- Cleared site and completed all F Gas paperwork.