Job Description: Detailed Pressure Leak Test on Climaveneta Chiller

Area: Viaduct Gardens, London

Issue Identified: Following a recent attendance to site for maintenance, it was noted that the unit was running short of refrigerant and had no obvious leaks. We attended to complete a detailed Pressure Leak Test (PLT) on the chiller to locate and fix the leak.

Climaveneta Chiller

Works carried out:

  • Isolated the Climaveneta Chiller electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Pressure tested with OFN (oxygen free nitrogen) to locate leaks.
  • Repaired the leak by means of brazing, and retested with OFN.
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.