Job Description: Detailed Pressure Leak Test (PLT) on Ciat Chiller

Area: Pan Peninsular

Issue Identified: Following a recent attendance for a call out, the engineer reported that the system was low on refrigerant. We attended to carry out a detailed pressure leak test on the Ciat Chiller.

Ciat Chiller

Works carried out:

  • Isolated the Ciat Chiller unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Pressure tested with OFN (oxygen free nitrogen) to locate leak.
  • Repaired the leak found on the liquid valve and suction valve by means of brazing.
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.