Fujitsi Compressor Replacement
Job Description: Fujitsi Compressor Replacement
Area: Portman Street, London
Issue Identified: Following a recent attendance on site our engineer advised that the compressor on the Fujitsu unit had failed and required replacement.
Works carried out:
- Isolated the Fujitsu air conditioning unit electrically and mechanically.
- Recovered refrigerant into certified cylinder for storage on site.
- Weighed and confirmed the charge.
- Pressure tested with OFN (oxygen free nitrogen) to locate any possible leak.
- Replaced compressor.
- Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
- Re-charged with recovered refrigerant and trim charged with virgin refrigerant.
- Test ran and commissioned.
- Completed waste transfer note and handed to on-site representative.
- Completed F Gas records.

Some of the many Fujitsu Split units we support
- ASYG07KGTB
- ASYG07KMCC
- ASYG18KMTA
- ASYG07KPCA
- ASYG18KLCA
- ASYG07LUCA
- ASYG07LMCE
- ASYG30LMTA
- ASYG18LFCA
- ASYG09LLCE
- AOYG36LATT
- AOYG36LBTB
- AOYG72LRLA
- AJY040LBLAH
- AJY040LELAH
- AJY072GALBH
- AJYA90GALH
- AJY072LELAH
Abbreviations
HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test, PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning, HP – High Pressure, LP – Low Pressure