Low Pressure Check on Carrier Chiller

Low Pressure Check on Carrier Chiller

Job Description: Low Pressure Check on Carrier Chiller

Area: Ludgate Hill, London

Issue Identified:  Following a recent call out to site the engineer advised that the Carrier Chiller was running on low pressures and required a pressure leak test

Carrier Chiller 30XA

Works carried out:

  • Isolated the Carrier 30XA Chiller unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Pressure tested with OFN (oxygen free nitrogen) to locate leak.
  • Repaired the leak by means of brazing.
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.