Mitsubishi Air Conditioning Unit PLT on floor 36

Mitsubishi Air Conditioning Unit PLT on floor 36

Job Description:  Mitsubishi Air Conditioning Unit PLT on floor 36

Area: Isle of Dogs, London

Issue Identified:  Following a call out our engineer discovered the system had lost a full charge of the refrigerant and therefore required an extended pressure test using tracer gas.

Works carried out:

  • Isolated the Mitsubishi unit on the 36th floor electrically and mechanically.
  • Recovered refrigerant into certified cylinder for storage on site.
  • Weighed and confirmed the charge.
  • Pressure tested with OFN (oxygen free nitrogen) to locate any possible leak.
  • No leaks found so checked all floors and found room 3606 had a leak on the evaporator.
  • Due to the size of the access hatch, we were unable to access the unit.
  • A bigger hatch will need to be made to enable the unit to be removed and replaced.
  • Further works quoted.

ACES Group Can Also Supply and Install all Mitsubishi Air-Conditioning Units – Call Us On 01865 890996

Mitsubishi Mr Slim – is available as wall or floor mounted and is ideal for retail and offices

M Series –  a very versatile system and is suitable for retail and offices and is available using low GWP R32 refrigerant

Multi Split – the outdoor unit can connect between 2 and 11 indoor units.

City Multi VRV – ideal for larger premises who demand efficiency and high performance

City Multi HVRF – a multi hybrid VRV system which can provide heating in one area and cooling in another area of building

Some of the many Mitsubishi Split units we support
  • PUZ-ZM200/250YKA R32 Power Inverter Heat Pump
  • PUZ-M200/250YKA R32 Standard Inverter Heat Pump
  • PLA-ZM R32 Power Inverter Heat Pump
  • PLA-M R32 Standard Inverter
  • PLA-ZM R32 Power Inverter Heat Pump
  • PLA-M R32 Standard Inverter
  • PLA-SM R32 Inverter Heat Pump
  • PKA-M R32 Power Inverter Heat Pump
  • PKA-M R32 Standard Inverter Heat Pump
  • SLZ-M R32 Inverter Heat Pump
  • PEAD-M R32 Power Inverter Heat Pump
  • PEAD-M R32 Power Inverter Heat Pump
  • PEAD-M R32 Standard Inverter Heat Pump
  • PEAD-M R32 Standard Inverter Heat Pump
  • SEZ-M R32 Inverter Heat Pump
  • PEA-RP R410A Power Inverter Heat Pump
  • PEA-RP R410A Standard Inverter Heat Pump
  • PAC-IF013B-E Air Handling Unit Controller
Abbreviations

HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test,  PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning,  HP – High Pressure, LP – Low Pressure