PLT and Coil Replacement on a Carrier Chiller

PLT and Coil Replacement on a Carrier Chiller

Job Description: PLT and Coil Replacement on a Carrier Chiller

Area: West Hampstead Square, London

Issue Identified:  Following our recent call out to site the engineer advised that the Carrier Chiller is running on low pressures and there were oil leaks around the coils.

Carrier Chiller

Works carried out:

  • Isolated the Carrier 30RB Chiller unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Pressure tested with OFN (oxygen free nitrogen) to locate leak.
  • Repaired the leak by means of brazing.
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.