Pressure Leak Test on a Daikin Chiller

Pressure Leak Test on a Daikin Chiller

Job Description: Pressure Leak Test on a Daikin Chiller

Area: Samuel House, London

Issue Identified:  Following a recent call out to site, we quoted to carry out a pressure leak test and charge confirmation.

HVAC Pressure Leak Test

Works carried out:

  • Isolated the Daikin Chiller unit electrically and mechanically.
  • Recovered 19kg of R134A refrigerant into a dedicated recovery cylinder.
  • Leak located on filter drier housing end plate.
  •  Changed the filter drier and fitted a new gasket.
  • Pressure tested with OFN (oxygen free nitrogen) to 10 bar for 2 hours.
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system.
  • Re-charged with the recovered refrigerant and trim charged to 25kg with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.