Pressure Leak Test on Aermec Chiller

Pressure Leak Test on Aermec Chiller

Job Description: Pressure Leak Test on Aermec Chiller

Area: Mark Lane, London

Issue Identified:  Following a call out the engineer advised that the Aermec Chiller is tripping on LP (low pressure), circuit 2. Engineer found a slight leak on the solenoid valve circuit 2.

Aermec Chiller

Works carried out:

  • Isolated the Aermec Chiller electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  •   Removed and replaced coil.
  • Pressure tested with OFN (oxygen free nitrogen) to locate leak.
  • Repaired the leak by means of brazing.
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.