Pressure Leak Test on Mitsubishi Heat Pump

Pressure Leak Test on Mitsubishi Heat Pump

Job Description: Pressure Leak Test on Mitsubishi Heat Pump

Area: Eagle Place, London

Issue Identified: Following a recent maintenance on site, the engineer had advised that the residential heat pump was running with low pressures and required a pressure leak test.

Mitsubishi Split System

Works carried out:

  • Isolated the Mitsubishi Heat Pump electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Checked and confirmed the charge.
  • Pressure tested the system with OFN (oxygen free nitrogen) and checked confirmed leak.
  • Repaired leak by means of brazing found on Schrader fitting.
  • Once proved released OFN to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charged with refrigerant.
  • Test Ran and re-commissioned.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas records.