Pressure Leak Test (PLT) on Carrier Chiller

Pressure Leak Test (PLT) on Carrier Chiller

Job Description: Pressure Leak Test (PLT) on Carrier Chiller

Area: Eastbourne Terrace, London

Issue Identified: Following a maintenance on site the engineer advised that circuit A and circuit B of the Carrier Chiller  both had a lot of oil marks on the condenser coils and requireda  pressure leak test and charge confirmation.

Additional benefits are: Both circuits were carried out one after the other to minimise disruption to the client.

Pressure Leak Test

Works carried out:

  • Isolated the Carrier Chiller unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Weighed and confirmed charge in the circuit.
  • Charged the unit with OFN (Oxygen free Nitrogen).
  • Checked the unit for leaks and report.
  • Further quotations for the leak repairs for circuit B were submitted at this stage, as it required condenser coils, the circuit was left off. Circuit A was repaired by means of tightening and recharged with recovered and virgin refrigerant.
  • Reports and F Gas paperwork were handed to client.