Pressure Leak Test (PLT) on Daikin VRV System

Pressure Leak Test (PLT) on Daikin VRV System

Job Description: Pressure Leak Test (PLT) on Daikin VRV System

Area: Duke Street, London

Issue Identified: Following a recent call out to the site for U9 fault, the engineer checked and cleared the fault. Once he started turning the units back on a new fault was noted on display. The new fault was U0, this fault is a low refrigerant warning. The engineer checked the running pressures, and they were low. The unit required a pressure leak test to investigate the location of the leak.

Daikin VRV

Works carried out:

  • Recovered any remaining refrigerant from the Daikin VRV into the certified cylinder.
  • Weighed and confirmed the system charges.
  • Charged the system with OFN (oxygen free nitrogen).
  • Leaks found and repaired by means of tightening.
  • Once proven the unit was leak-tight we released the nitrogen.
  • Evacuated system to a minimum of 2 Torr.
  • Re-charged the unit with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed all waste paperwork.
  • Cleared site of any waste created.