Job Description: Pressure Leak Test (PLT) on Daikin VRV

Area: Charles II Street, London

Issue Identified: Following a recent call out at the site for the F3 fault, the engineer advised that the temperature in the oil separator was very high and there seemed to be a lack of oil flow to the system. This indicated refrigerant shortage in the system, which is why we completed a Pressure Leak Test (PLT).

Daikin VRV

Works carried out:

  • Isolated the Daikin VRV unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Pressure tested with OFN (oxygen free nitrogen) to locate leak.
  • Repaired the leak by means of brazing.
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.