Job Description: Pressure Relief Valve Replacement on a Ciat LWN Chiller

Area: St James Street, London

Issue Identified:  Following a recent attendance on site, the engineer reported that there are some PRV’s which required replacing on the Ciat Chiller

Works carried out:

  • Isolated the Ciat Chiller unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Removed and replaced the PRV’s with Castel Pressure Relief Valves.
  • Pressure tested with OFN (oxygen free nitrogen).
  • Once proved released Oxygen Free Nitrogen (OFN) into atmosphere and evacuated the system to a minimum of 2 Torr.
  • Re-charged with the recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed a waste transfer note and handed to on-site representative.
  • Completed an F Gas certificate.

Some of the many Ciat Chillers we support
  • AQUACIAT POWER ILD R32
  • AQUACIAT LD R32
  • AQUACIAT POWER LD R32
  • POWERCIAT LX R134a
  • AQUACIAT LD R410A
  • AQUACIAT Free Cooling
  • AQUACIAT Power R410A
  • CIAT Cooler R-410A
  • AQUACIAT2 HYBRID R-410A
  • AQUACIAT Caleo
  • GEOCIAT Modular
  • DynaCIAT Power
  • HydroCIAT LW
  • HydroCIAT TURBO LWT

ACES Also Supply And Install New Chillers – Call Us For More Information 01865 890996

Ciat Chiller Features

The AQUACIAT Chillers have been adapted for heating and air conditioning applications in the fields of Offices, Healthcare, Industry, Administration, and Commercial  buildings.

These units are designed for outdoor installation and do not require protection from adverse weather conditions.

To operate in COOLING or HEATING mode, these units use outside air as the only external source, this permits the evacuation of heat in summer or the supply of thermal energy for heating in winter.

Abbreviations

HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test,  PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning,  HP – High Pressure, LP – Low Pressure

Ref: 1313