PRV Replacement for 3 x Uniflair Chillers

PRV Replacement for 3 x Uniflair Chillers

Job Description: PRV Replacement for 3 x Uniflair Chillers

Area: Overton Mill, Hampshire

Issue Identified:  Following a recent visit to site, we quoted for the replacement of the PRV on the 3 x chillers

Uniflair Chiller

Works carried out:

•     Isolated the Uniflair Chiller units electrically and mechanically.
•    Closed the discharge and liquid service valves and decanted the charge over to the evaporator side of the system.
•    Replaced Pressure Relief Valves. PRV’s fitted were: High Side PRV 2 x 20 bar 1/2″ x 1″ g14/s 2 x 20 bar 1″ x 1-1/4″ g20/s Low Side Manifold 2 x 16bar  3/4″-1″ g14/s.
•    Re-charged the Uniflair Chillers.
•    Test ran and re-commissioned.
•    Completed a waste transfer note and handed to on-site representative.
•    Completed an F Gas certificate.