Remanufactured York Screw Compressor DXS36LASA 46/50 Replacement on a York Chiller

Remanufactured York Screw Compressor DXS36LASA 46/50 Replacement on a York Chiller

Job Description: Remanufactured York Screw Compressor DXS36LASA 46/50 Replacement on a York Chiller

Area: Parliament Street, London

Issue Identified: Client requested quote to replace failed compressor

York Chiller

Scope of Works Carried Out:

  • Aces engineers removed access panels & acoustic enclosures to allow for compressor removal.
  • Isolated and locked off chiller 2 system 1 following relevant LOTO (lockout tagout) procedures.
  • Isolated system 1 compressor and decanted refrigerant into specialist receiver cylinders.
  • Disconnected failed compressor ready for removal by ACES lifting teams.
  • ACES Specialist Lift & Shift assisted with removal and refitted York Remanufactured Compressor.
  • Reconnected replacement compressor mechanically and electrically.
  • Leak tested using OFN (oxygen free nitrogen) to prove integrity.
  • Evacuated system once proven.
  • Recharged with reclaimed refrigerant.
  • Returned York Chiller to normal operation.
  • Re-installed access panels and acoustic enclosures.
  • Completed F Gas paperwork and handed to on-site representative.
  • Cleared site of all rubbish