Repairs to a Geoclima Chiller
Job Description: Repairs to a Geoclima Chiller
Area: Bath Road, Hounslow
Issue Identified: Following a recent planned preventative maintenance visit our engineer advised that circuit 2 of the Geoclima chiller was completely void of refrigerant. Pressure leak test required to investigate issues.
Works carried out:
- Isolated the Geoclima Chiller unit electrically and mechanically.
- After investigation it was found that the internal pressure gauges had ruptured.
- Isolated the gauges.
- Recovered refrigerant into certified cylinder for storage on site.
- Weighed and confirmed the charge.
- Pressure tested with OFN (oxygen free nitrogen) to locate any possible leak.
- Found a couple of small leaks on schrader valves which were tightened and sealed, system held pressure.
- Released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
- Re-charged with recovered refrigerant and trim charged with virgin refrigerant.
- Test ran and commissioned.
- Completed waste transfer note and handed to on-site representative.
- Completed F Gas records.

ACES Group Can Also Supply and Install New Chillers – Call Us On 01865 890996
Geoclima Chillers have a wide range of models with capabilities for sustainable refrigerant options. With non-ozone depleting refrigerant, excellent efficiency and powerful controls, these units are ideal for applications where temperature control is crucial. Geoclima Chillers have been designed to bring efficient, reliable cooling to all types of large commercial applications. ACES engineers are experts in service and maintenance of all Geoclima Chiller types. We have engineers based in London 24/7.

Some of the many Geoclima Chillers we support
- Geoclima GHA
- Geoclima GHA ES
- Geoclima GHA FC
- Geoclima GSA
- Geoclima GHH
- Geoclima GSE
- Geoclima VHA CM
- Geoclima VHA
- Geoclima VHA FC
- Geoclima VSA
- Geoclima VHH
- Geoclima VSE
- Geoclima TMA
- Geoclima TMA CM
- Geoclima TMA ES
- Geoclima TMA FC
- Geoclima TSA
- Geoclima TMH
- Geoclima TSE
- Geoclima RCE
Abbreviations
HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test, PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning, HP – High Pressure, LP – Low Pressure