Repairs to a York Chiller YCAL0827SBXA

in Chiller Repairs 

Asset: York Chiller YCAL0827SBXA

Area: Charles Street, London

Issue Identified: Following the recent maintenance visit on site it was noted that the PRV’s were out of date. Circuit 1 was in LP alarm which  indicated there was a refrigerant leak on the system.

Works Carried Out:

  • Isolated the unit electrically and mechanically.
  • Recovered the refrigerant into a dedicated recovery cylinder.
  • Renewed Pressure Relief Valves.
  • Pressured tested with OFN (oxygen free nitrogen) to locate leak.
  • Once proved released OFN to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charged with virgin refrigerant.
  • Test ran and re-commissioned
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas certificate.