Replace Coil on a Denco CRAC Unit

Job Description: Replace Coil on a Denco CRAC (critical room air-conditioning) Unit

Area: St James Market, London

Issue Identified: Following a call out to site the engineer advised that there was a leak on the coil of the Denco unit and required to be replaced.

Denco Coil

Works carried out:

  • Isolated the Denco unit electrically and mechanically.
  • Recovered the refrigerant from the Denco unit into a dedicated recovery cylinder.
  • Removed the coil from the Denco CRAC (critical room air-conditioning) Unit.
  • Installed new coil.
  • Charged the system with OFN (oxygen free nitrogen) to prove leak tight for 24 hrs.
  • Once proved released the OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charged with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas certificate.