Replace Failed Coils on a Carrier Chiller

Replace Failed Coils on a Carrier Chiller

Job Description:  Replace Failed Coils on a Carrier Chiller

Area: Eastbourne Terrace, London

Issue Identified:  Following a pressure leak test our engineer found a leak on one of the condenser coils. The coil was dated August 08. There were also another 2 coils that were dated the same time and we recommended replacing these also.

Works carried out:

  • Released the nitrogen from circuit.
  • ACES Lift and Shift Team removed the failed coils from the chiller.
  • Installed new coils.
  • Charged the system with nitrogen to prove leak
  • Once proved release OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
  • Recharged the system with recovered refrigerant and topped up with virgin refrigerant.
  • Test ran and re-commissioned.
  • Completed waste transfer note and hand to on-site representative.
  • Completed F Gas register.

ACES Group Can Also Supply and Install New Chillers – Call Us On 01865 890996

Carrier Chillers have a wide range of models with capabilities for sustainable refrigerant options. With non-ozone depleting refrigerant, excellent efficiency and powerful controls, these units are ideal for applications where temperature control is crucial. Carrier Chillers have been designed to bring efficient, reliable cooling to all types of large commercial applications. ACES engineers are experts in service and maintenance of all Carrier Chiller types. We have engineers based in London 24/7.

Some of the many Carrier Chillers we support
  • AquaSnap® Air-Cooled Liquid Chiller 30 RAP
  • AquaSnap® Air-Cooled Liquid Chiller 30RB
  • AquaForce® Air-Cooled Screw Chiller 30XA
  • AquaForce® Variable Speed Air-Cooled Screw Chiller 30XV
  • AquaEdge® Water-Cooled, Custom-Design Centrifugal Chiller 17DA
  • AquaEdge® Water-Cooled Centrifugal Chiller 19DV
  • AquaEdge® High-Efficiency Semi-Hermetic Centrifugal Chiller 19XR
  • AquaEdge® High-Efficiency Variable-Speed Screw Chiller 23XRV
  • AquaForce® High-Efficiency Indoor Liquid Screw Chiller 30HX
  • AquaSnap® Indoor Water-Cooled/Condenserless Liquid Chiller 30MP
  • AquaForce® High-Efficiency, Water-Cooled, Indoor Liquid Screw Chiller 30XW
Abbreviations

HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test,  PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning,  HP – High Pressure, LP – Low Pressure