Replace Filter Driers on a Denco Unit
Job Description: Replace Filter Driers on a Denco Unit
Area: St James Market, London
Issue Identified: Following a recent call out our engineer discovered the system was going off on high discharge pressure, we found there is a temperature difference when recording temperatures across the filter drier.
Works carried out:
- Isolated the Denco unit electrically and mechanically.
- Recovered refrigerant into certified cylinder for storage on site.
- Weighed and confirmed the charge.
- Removed and replaced the filter driers.
- Pressure tested with OFN (oxygen free nitrogen) to locate any possible leak.
- Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
- Re-charged with recovered refrigerant and trim charged with virgin refrigerant.
- Test ran and commissioned.
- Completed waste transfer note and handed to on-site representative.
- Completed F Gas records.

ACES Group Can Also Supply and Install all Denco Units – Call Us On 01865 890996
ACES service and maintain Denco Units. Denco Chillers and Air-Conditioning units are used for a variety of applications including process cooling where tough demands are placed on all types of temperature conditions, strict control and constancy. ACES have engineers based in London 24/7 available for all call outs or maintenance work.

Some of the many Denco units we support
- DENCO-OfficeCool
- Adia-DENCO EVAPORATIVE COOLING UNIT
- Ultra-DENCO
- Row-DENCO
- Multi-DENCO
- GLCU 2015 – 4060 BC1/2 (40 – 162 kW)
- GCH 100 – 250 CD4/1 (13 – 32 kW)
- HeaMo GEO – REG 195-415 AD42 (200 – 426 kW)
- HeaMo GEO – REG 050-205 AD22 (50 – 212 kW)
- GLWH 2012–4120 CD2.R (38 – 400 kW) (reversible)
- GLWH 2012-4120 CD2.H (38 – 400 kW) (irreversible)
- GLWC 2012-4120 CD2 (38 – 400 kW)
- GLWC 1055-2475 DA2 (188 – 1693 kW)
- FGWC 2140-2465 AE2 (R513A, Inverter-Screw 532-1784 kW)
- GLRC 2015–4160 CD2 (41 – 442 kW)
- FGAH 1005-1014 CD 4/1 (Inverter 5-38kW)
- FGAH 2020-2081 AG 1/2 (R454B, 53 -223 kW)
- FGAH 4060-4120 BG2 (R454B, 151 – 337 kW)
- GLFC 2150-2600 DA2 (286 – 1212 kW)
- HeaMo Air – REA 145-300 AD42 (142-311 kW)
Abbreviations
HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test, PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning, HP – High Pressure, LP – Low Pressure