Replace Inverter Compressor on a Daikin VRV

Replace Inverter Compressor on a Daikin VRV

Job Description:  Replace Inverter Compressor on a Daikin VRV

Area: Old Broad Street, London

Issue Identified:  Following a recent attendance on site our engineer advised that the inverter compressor on the Daikin VRV unit had failed and required replacement.

Works carried out:

  • Isolated the Daikin VRV unit electrically and mechanically.
  • Recovered refrigerant into certified cylinder for storage on site.
  • Weighed and confirmed the charge.
  • Tested the oil for acidity.
  • Replaced the compressor and PCB board using hot works.
  • Pressure tested with OFN (oxygen free nitrogen) to locate any possible leak.
  • Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charged with recovered refrigerant and trim charged with virgin refrigerant.
  • Test ran and commissioned.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas records.

ACES Group Can Also Supply and Install New Air-Conditioning Units – Call Us On 01865 890996

Some of the many Daikin Units we support

– RXM-R
– ARXM-R
– FTXG-LS
– FVXS-F
– FTXS-K
– CTXM-R
– FVXM-F
– FTXG-LW
– CTXM-M
– CTXS-K
– RXS-L
– FTXS-G
– RXS-L3
– ARXS-L
– FDXS-F9
– ARXS-L3
– FDXS-F
– RXM-R
– FDXM-F
– ARXM-R
– FLXS-B
– FLXS-B9
– CTXM-N
– RXYSA-AY1
– FCAG-B
– LRNUN-AY1
– CTXA-AW
– FCAHG-H
– FXFQ-B
– RZQG-L(8)Y1
– RZAG-A
– CTXA-BS
– RZAG-MV1
– 2AMXF-A
– 3MXM-N9
– 3MXM-N
– 2MXM-M9
– 5MXM-N9
– 5MXM-N
– 2MXM-M
– 4MXM-N9
– 2MXM-N
– 5MXM-M
– 4MXM-M
– RXYQ-T9
– RYMQ-U
– RYYQ-U
– FXFA-A
– RXYSA-AY1
– FXFQ-A
– RWEYQ-T8
– RYYQ-T8
– RXYQ-U
– RXYQ-T8
– RQYQ-P

Daikin Air-Conditioning Systems designed for comfort and efficiency. Prominent in small, medium, and large offices. Daikin air curtains minimise hot and cold air loss. Fully flat cassettes integrate seamlessly into false ceilings and will not disturb office concentration with its quiet operation. ACES engineers specialise in service and maintenance of indoor and outdoor Daikin units.


Abbreviations

HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test,  PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning,  HP – High Pressure, LP – Low Pressure