Replace Mitsubishi Air Conditioning Units
Job Description: Replace Mitsubishi Air Conditioning Units
Area: Alfred Place, London
Issue Identified: Following a recent attendance on site our engineer advised that the 6th floor units had suffered an electrical failure. The units had a lot of power boards that had failed.
Works carried out:
- Isolated the old Mitsubishi unit electrically and mechanically.
- Recovered any remaining refrigerant.
- Removed and replaced the outdoor unit.
- Removed and replaced the isolators.
- Removed and replaced the indoor unit.
- Checked and installed new pumps as required.
- Pressure tested with OFN (oxygen free nitrogen) to confirm the pipework integrity.
- Once proved released OFN to atmosphere and evacuated system to a minimum of 2 Torr.
- Reinstated power and commissioned the unit.
- Repeated for further 3 units.

ACES Group Can Also Supply and Install all Mitsubishi Air-Conditioning Units – Call Us On 01865 890996
Mitsubishi Mr Slim – is available as wall or floor mounted and is ideal for retail and offices
M Series – a very versatile system and is suitable for retail and offices and is available using low GWP R32 refrigerant
Multi Split – the outdoor unit can connect between 2 and 11 indoor units.
City Multi VRV – ideal for larger premises who demand efficiency and high performance
City Multi HVRF – a multi hybrid VRV system which can provide heating in one area and cooling in another area of building

Some of the many Mitsubishi Split units we support
- PUZ-ZM200/250YKA R32 Power Inverter Heat Pump
- PUZ-M200/250YKA R32 Standard Inverter Heat Pump
- PLA-ZM R32 Power Inverter Heat Pump
- PLA-M R32 Standard Inverter
- PLA-ZM R32 Power Inverter Heat Pump
- PLA-M R32 Standard Inverter
- PLA-SM R32 Inverter Heat Pump
- PKA-M R32 Power Inverter Heat Pump
- PKA-M R32 Standard Inverter Heat Pump
- SLZ-M R32 Inverter Heat Pump
- PEAD-M R32 Power Inverter Heat Pump
- PEAD-M R32 Power Inverter Heat Pump
- PEAD-M R32 Standard Inverter Heat Pump
- PEAD-M R32 Standard Inverter Heat Pump
- SEZ-M R32 Inverter Heat Pump
- PEA-RP R410A Power Inverter Heat Pump
- PEA-RP R410A Standard Inverter Heat Pump
- PAC-IF013B-E Air Handling Unit Controller
Abbreviations
HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test, PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning, HP – High Pressure, LP – Low Pressure