Replace Schrader Valve on a Climaveneta Chiller
Job Description: Replace Schrader Valve on a Climaveneta Chiller
Area: Nine Elms, London
Issue Identified: Following a recent maintenance our engineer found circuit 1 sight glass flashing indicating that the system was short of refrigerant.
Works carried out:
- Isolated the Climaveneta Chiller unit electrically and mechanically.
- Recovered refrigerant into certified cylinder for storage on site.
- Weighed and confirmed the charge.
- Pressure tested with OFN (oxygen free nitrogen) to locate any possible leak.
- Replaced schrader valve and re-pressure tested overnight.
- Once proved released OFN (oxygen free nitrogen) to atmosphere and evacuated system to a minimum of 2 Torr and carried out a rise test.
- Re-charged with recovered refrigerant and trim charged with virgin refrigerant.
- Test ran and commissioned.
- Completed waste transfer note and handed to on-site representative.
- Completed F Gas records.

ACES Group Can Also Supply and Install New Chillers – Call Us On 01865 890996

Some of the many Climaveneta Chillers we support
- Air-cooled chiller BRA 0011 – 0061
- Air-cooled chiller BRAT 0011 – 0121
- Air-cooled chiller MICS 0072 – 0182
- Air-cooled chiller FOCS60 /K 0751 – 2632
- Air-cooled chiller NECS 0202T-0612T
- Air-cooled chiller NX 0152P – 0812P
- Air-cooled chiller NECS-C 0152-1204
- Air-cooled chiller NX 0614T -1214T
- Air-cooled chiller NECS-FC 0152 -1604
- Air-cooled chiller FOCS 0751 – 2632
- Air-cooled chiller FOCS 1542 – 2642
- Air-cooled chiller NECS 1314-3218
- Air-cooled chiller FOCS-XL 1502 – 6002
- Air-cooled chiller i-FX (1+i) 2602 – 5403
- Air-cooled chiller FOCS2/K 1502 – 8404
- Air source heat pump NECS-W 0152-1204
- Air source heat pump FOCS-W 0401 – 1902
- Air source heat pump TECS2-W 0251 – 1954
- Air source heat pump FOCS2-W 1301-9604
Abbreviations
HVAC – Heating, Ventiliation and Air Conditioning, PLT – Pressure Leak Test, PRV – Pressure Relief Valve, PPM – Planned Preventative Maintenance, OFN – Oxygen Free Nitrogen, AHU – Air Handling Unit, GWP – Global Warming Potential, VRF – Variable Refrigerant Flow, VRV – Variable Refrigerant Volume, ACU – Air Conditioning Unit, FCU – Fan Coil Unit, AC – Air Conditioning, HP – High Pressure, LP – Low Pressure