Replacement Screw Compressor on Liebert Chiller

Replacement Screw Compressor on Liebert Chiller

Job Description: Replacement Screw Compressor on Liebert Chiller

Area: Hounslow, London

Issue Identified: Following critical failure of component we replaced the screw compressor on the chiller to get both circuits running again.

Liebert Chiller

Works carried out:

  • Isolated the Liebert Chiller electrically and mechanically.
  • Decanted the system into cylinders and weighed for F gas records.
  • Removed the compressor and installed new with the Lift and Shift team.
  • Pressurised the system with OFN (oxygen free nitrogen) overnight and checked for leaks.
  • Repaired any leaks found and replaced 3 contactors.
  • Evacuated the system.
  • Returned the original charge of refrigerant to the system, test ran and commissioned.
  • Cleared site and completed all F Gas paperwork.