Specialist Engineering Works at One New Change, London

in Compressor Replacement 

Facilitate the replacement of 1 x clients own screw compressor in addition to ancillary works on a Trane Chiller

  • Chiller #3 compressor 2B disconnected electrically and removed and attached pipework ready for removal from the chiller.
  • Refrigerant removed from chiller 4 circuit 2.
  • Installed the overhauled Trane Compressor onto circuit B.
  • Reconnected pipework and electrical connections.
  • Pressure tested.
  • Reinstated power to the compressor so the crank case heaters were on.
  • Evacuated circuit down to 2 torr.
  • Ran the chilled water pump and put back the recovered refrigerant charge.
  • Replaced the compressor star delta contactors.
  • Carried out a dry run of the compressor to check the star delta contactor sequence was working ok.
  • Test ran compressor 2B.