Transducer Repair on York Chiller

Transducer Repair on York Chiller

Job Description: Transducer Repair on York Chiller

Area: Mitcham, London

Issue Identified: Following a recent maintenance on site, the engineer had advised that the transducer on the York chiller required repair, with a Pressure Leak Test (PLT) to be carried out at the same time.

York Chiller

Works carried out:

  • Isolated the York Chiller unit electrically and mechanically.
  • Recovered refrigerant into a dedicated recovery cylinder.
  • Checked and confirmed the charge.
  • Repaired transducer.
  • Pressure tested the system with OFN (oxygen free nitrogen) and checked to confirm leak.
  • Repaired any leaks by means of brazing.
  • Once proved released OFN to atmosphere and evacuated system to a minimum of 2 Torr.
  • Re-charged with refrigerant.
  • Test Ran and re-commissioned.
  • Completed waste transfer note and handed to on-site representative.
  • Completed F Gas records.